The P5 universal dry media pressure transmitter accurately measures multiple ranges optimized for building (zone) pressure, filter measurement, and static duct applications. Selectable outputs and uni/bi-directional readings reduce inventory. Innovative probe integrates with unit or can be mounted remotely for static pressure. Optional LCD for panel mount readings and set up. PATENTED DESIGN
- Building (zone) pressure
- Filter condition measurement
- Duct/static
|
Power Supply |
12-30VDC/24VAC(1), 30mA max | |
|
Output type |
Selectable outputs |
4-20mA loop powered, 4-20 mA 3-wire, 0-5VDC, 0-10VDC |
|
Output scaling |
P5-0100 |
0-1” (Selectable 0.1, 0.25, 0.5, 1.0, ±0.1, ±0.25, ±0.5, ±1.0 “WC) |
| Operating Temperature | Operating range Compensated range | -4 to 140F (-20 to 60ºC) -4 to 140F (-20 to 60ºC) |
| Media compatibility |
Dry, oil-free air, N2 |
|
|
Sensor Type |
MEMS silicon piezoresistive; precision calibrated |
|
|
Sensor Performance |
Accuracy |
±1.0% of selected range (combined linearity and hysteresis) |
|
Agency |
Compliance |
CE, RoHS |
|
Enclosure |
Flammability |
UL94 5VB |
|
(1) One side of transformer secondary is connected to signal common. Dedicated transformer is recommended. |