ECMset Current Switch

Higher Reliability, Faster Installation, Superior Accuracy | Sense the Difference
Adjustable minimum turn-on
Prevents false trip due to ECM stand-by current
Split-core operation to 200A
N.O. 30VAC/DC output
Optional command relay with LED

  • Reliable operation on ECM motors
  • Set trip point with easily scaled dial to that sensor only turns on when motor is actually running
  • Super low turn-on adjustment scale Maintenance-free—no call backs
  • No hazardous guesswork. Multi-turn adjustments are a thing of the past
  • Reduce the risk of arc flash; sensor can be set without calibration in live enclosure
  • Industry leading 7 year warranty

Ask for a quotation

ECMSet™ is designed for no/go run detection on electronically commutated motors (ECMs) . ECMs draw a small amount of AC standby current to power their inverter, up to 1A, even when the motor isn’t running. The ECMSet features a high resolution adjustable turn-on setpoint to ignore standby current, preventing false ON status indications.

  • No/go run detection for EC motors
  • On set-point prevents false trips due to EC inverter stand-by current
  • Great for data center current switch sensing

Standard Output Rating

1.0A@30VAC/DC

Output Type

NO, solid-state FET

Environmental Rating

5-140 °F (-15-60 °C)
10-90% RH Non-condensing

Insulation Class

600V RMS. For use on insulated conductors only! Use minimum
75 ° C insulated conductor

Sensor Power

Induced

Frequency Range

50/60Hz

Dimensions (LxWxH)

2.94"x 2.23" x 0.82" (1.4"H with optional relay module)

Sensor Aperture

0.75"

Compliance

cUL, UL, CE, RoHS

RELATED PRODUCTS